Getting Started
2-12
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
SM 322: Short Circuit to L+
1. Open the front door of the DO module and use a wire to short-circuit the digital
output 0 (terminal 3) to L+ (terminal 1).
2. Watch the status LEDs.
IM 153-2:
SF: comes on
SM 322; DO 8 x 24 V DC/0.52 A:
SF: comes on Diagnostic message has been issued
F0: comes on Channel error
0: Off Output is not active
3. Evaluate the diagnostic message.
Result:
Station status 1: Byte x.3 is set External
diagnostics
Module diagnosis Byte (x+7).4 is set Slot 5
Channel-specific diagnosis:
Byte (x+16).0 to (x+16).5: 000100
B
Slot 5
Byte (x+17).0 to (x+17).5: 000000
B
Channel 0
Byte (x+18).0 to (x+18).4: 00001
B
Short circuit
4. Remove the wire between terminal 3 and terminal 1.
Evaluate the diagnostic LEDs again.
IM 153-2:
SF: Off
SM 322; DO 8 x 24 V DC/0.52 A:
SF: Off
F0: Off
0: On
The diagnostic message is erased.