Commissioning and Diagnostics
6-20
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
Table 6-8 Structure of station status 1 (Byte 0), continued
Bit Cause/RemedyMeaning
6 1: The DP slave type does not corres-
pond to the software configuration.
Compare the desired configuration with the
actual configuration.
7 1: Parameters have been assigned to
the DP slave by a different DP ma-
ster (not that which currently has
access to the DP slave).
The bit is always 1 when you are accessing
the DP slave using the programming device
or another DP master, for example.
The PROFIBUS address of the DP master
that parameterized the DP slave is located
in the ”master PROFIBUS address”
diagnostic byte.
Station status 2
Table 6-9 Structure of station status 2 (Byte 1)
Bit Meaning
0 1: New parameters have to be assigned to the DP slave.
1 1: The slave is in start-up phase.
2 1: The bit is always at 1 in the DP slave.
3 1: Response monitoring has been enabled for this DP slave.
4 1: The DP slave has received the ”FREEZE” control command.
5 1: The DP slave has received the ”SYNC” control command.
6 0: The bit is always at 0.
7 1: The bit is always at 0.
Note: When the station status is read by the DP master, the bit is ”1” if
the DP slave in the DP master has been deactivated.
The DP slave is deactivated – that is, it has been removed from current
processing.
Station status 3
Table 6-10 Structure of station status 3 (Byte 2)
Bit Meaning
0 to 6 0: The bits are always at ”0”.
7 1: There are more channel-specific diagnostic messages than can be
represented in the diagnostic frame.