Product Information for Distributed I/O Device ET 200M, Manual
A5E00272208-01
3
1 On Section 1.3 and 9.2
Further information for IQ-Sense
As from Firmware Version V3.0.1 IQ-Sense is supported by the IM 153-2Bx00.
The following supplements result for the function tables:
For Table 1-2
Interface Module With Order Number 6ES7 ...
Functions /
Properties
153-1AA.. 153-2Ax.. 153-2Bx..
IQ-Sense – x
(as from firmware
V3.0.1)
For Table 9-2
Interface Module With Order Number 6ES7 ...
153-2AA.. 153-2BA.. 153-2AB..
(FO)
153-2BB..
(FO)
Functions /
Properties
00 01 02 00 00 01 00
IQ-Sense – x
(as from
firmware
V3.0.1)
– – x
(as from
firmware
V3.0.1)
2 On Section 3.5
Further information on redundancy with IM 153-2
You can operate the IM 153-2 redundantly
At an SIMATIC S7-400H (e.g. CPU 417-4H)
With a GSD file at any DP masters (e.g. S5-115H)
In case of configuration with a GSD file, redundant operation of the IM 153-2
can only be carried out in the DPV0 operating mode. Setting of this operating
mode is carried out differently depending on the configuring tool used.
With software redundancy
The optional software "SIMATIC S7 Software Redundancy" is required in
addition to the STEP 7 basic package.
Conforming to standard
Specification System Redundancy (SR) V1.0, Dec. 2001 of the PROFIBUS
user organization