Siemens SIMATIC Distributed I/O System DP/ASi Link Specifiche Pagina 184

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 240
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 183
Technical Specifications
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
8.5.2 Use of the ET 200M / S7-300 in a Zone 2
Hazardous Area
Zone 2
Hazardous areas are divided up into zones. The zones are distinguished according
to the probability of the existence of an explosive atmosphere.
Zone Explosion Hazard Example
2
Explosive gas atmosphere
occurs only seldom and for a
short time
Areas around flange joints with flat
gaskets in pipes in enclosed spaces
Safe area No
Outside zone 2
Standard distributed I/O applications
Below you will find important information on the installation of the ET 200M
distributed I/O device and the SIMATIC S7-300 in a hazardous area.
Further Information
You will find further information on the ET 200M and the various S7-300 modules in
the manual.
Production Location
Siemens AG, Bereich A&D
Werner-von-Siemens-Straße 50
92224 Amberg
Germany
Certification
II 3 G EEx nA II T3 .. T6 to EN 50021 : 1999
Test number: KEMA 02ATEX1096 X
Note
Modules with II 3 G EEx nA II T3 .. T6 certification can only be used in
SIMATIC S7-300/ET 200M automation systems belonging to equipment
category 3.
Vedere la pagina 183
1 2 ... 179 180 181 182 183 184 185 186 187 188 189 ... 239 240

Commenti su questo manuale

Nessun commento