Compatibility Between the IM 153-x Modules
9-2
Distributed I/O Device ET 200M
EWA-4NEB780600602-06
9.1 Compatibility Between the Versions of the IM 153 and
IM 153-1
The Versions of the IM 153-1
Table 9-1 Features and variants of the IM 153-1
Functions/Features
Interface Module and Order Number 6ES7 ...
153-1AA..
00 01 02 03 82 83
Minimum interval between two slave list cycles 1 ms 0.1 ms 0.1 ms 0.1 ms 0.1 ms 0.1 ms
SYNC, FREEZE
Module change during operation
Direct communication as of
E07
as of
E06
Enhanced diagnostics
64-byte diagnostic frame
As of
E02
Extended range of environmental conditions
(outdoors)
RC network with 10 M for ungrounded
configuration (see Sections 5.1.3 and 9.3)
(1 M)
(1 M)
as of
E08
as of
E07
DPV1 mode as of
E05
as of
E03
E Version
Compatibility Between 153-1AA00- and 153-1AA01-...
The IM 153-1 (order number 6ES7 153-1AA01-0XB0) is partially downward
compatible. This means you can also use the configuration and the user program
for the IM 153-1 (order number 6ES7 153-1AA01-0XB0) for the IM 153 (order
number 6ES7 153-1AA00-0XB0), except if SYNC and FREEZE are used in these
user programs. Note the different Min_Slave_interval (see Table 9-1).
Upgrading to 153-1AA02-...
You can pay to have the IM 153-1 (order number 6ES7 153-1AA01-0XB0)
upgraded to the IM 153-1 (order number 6ES7 153-1AA02-0XB0).
For more information, get in touch with your Siemens partner.