CP 523 Summary
A.3 Feedback Information in Print Mode
Table A-5. Status of the Module in Print Mode (Byte 0) ( 6.6)
X= Signal state not significant for other half-byte
Byte 0
Status
Bits
4 to 7 0 to 3
Detailed Explanation
0
X
X
0
1
No error
Defective memory
submodule
Job buffer empty
2 No texts configured
No message texts configured on the memory
submodule
X 3 Entries in job buffer
7 No battery backupX Either
- No battery has been inserted in the power
supply module or
- The battery is defective
X 8 Job buffer/message
buffer full
The module cannot service any further print requests
at present.
The request must be repeated.
F CP in restart routine0 Message appears only on restart.
The clock data is invalid.
The module cannot accept any job requests.
1 X Clock defective Replace module
2 X Default clock time set The clock is preset with the values Sunday, 1:1:90,
12:00:00.
3 X Time of day/date error At least one setting is outside the permissible range.
The clock has not accepted the new clock data and is
continuing with the current data.
8 X Hardware fault Replace module
4 X Illegal job request You have submitted a request to the CP which is not
permissible in Print mode ( 6.7).
EWA 4NEB 811 6044-02a