CP 523 Communications Mode
Example: Transferring parameter setting data for parameter block 7
Start address 128 is set on the CP 523. The module is to be operated in Interpretive mode. The
message frames to be transmitted have different lengths; the end of the message frame is
therefore signalled with 0D0D
H
(0D0D
H
=two carriage returns). The character delay time may be
300 ms (300 ms=001E
H
).
* 5.2
** FB 99 waits until the CP 523 can accept job requests ( 4.1)
STL FB 114STL OB 22 Explanation
:JU FB 99
NAME :SYNC **
:JU FB 112
NAME :BLOCK7
:BE
Load end characters into ACCUM 1 and
transfer to CP in bytes 6 and 7.
Load message frame length into
ACCUM 1 and transfer to CP in bytes 4
and 5.
Load character delay time into ACCUM 1
and transfer to CP in bytes 2 and 3.
Load job number (90
H
), parameter block
number (7
H
) and mode code (2
H
) into
ACCUM 1 and transfer to the CP.
NAME :BLOCK7
:L KH ODOD
:T PW 134
:L KH 0000
:T PW 132
:L KH 001E
:T PW 130
:L KH 9072
:T PW 128 *
:BE
Note:
The status byte can be scanned approx. 30 ms after the request was issued to check whether
correct parameter values were forwarded (X4 is returned to indicate false values ( 7.4.1)).
EWA 4NEB 811 6044-02a
7-37