Siemens SIMATIC NET PROFIBUS Manuale di Servizio Pagina 184

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 238
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 183
Description of the DP Functions, Data, and Error Codes
DP Base Programming Interface for CP 5613/CP 5614
184
C79000-G8976-C108-01
Byte 2 (Alarm_Type Variant)
Bit Meaning
7 Value Meaning
0 Alarm
6 to 0
Alarm_Type
0 = reserved
1 = Diagnostic alarm
2 = Process alarm
3 = Pull alarm
4 = Plug alarm
5 = Status alarm
6 = Update alarm
7-31 = reserved
32-126 = Vendor-specific
127 = reserved
Byte 2 (Status_Type Variant)
Bit Meaning
7 Value Meaning
1 Status message
6 to 0
Status_Type
0 = reserved
1 = Status message
2 = Module status
3-31 = reserved
32-126 = Vendor-specific
127 = reserved
Byte 3 (Slot Number Variant)
Bit Meaning
7 to 0 Slot number