4.2.9 DPS_set_diag
Purpose
This function transfers diagnostic data to the DP slave module. The CP 5614 slave
module passes on the data to the master that controls it.
Note
The length of the diagnostic data can vary during operation!
The 6 standard diagnostic bytes are managed by the CP 5614 slave module itself.
For more information on the structure and formats of diagnostic information see
Section 4.6.
Syntax
DPR_DWORD DPS_set_diag(DPR_DWORD user_handle, // in
DPR_BYTE *user_diag_data, // in
DPR_WORD user_diag_len, // in
DPR_WORD diag_state, // in
DP_ERROR_T *error ); // out