Appendix E: Device Data Format
Siemens Energy & Automation, Inc. 85
Alarm Status 22 Bit Contents
15 Overvoltage Setpoint
14 Voltage Unbalance Setpoint
13 Undervoltage Setpoint
12 Current Unbalance Setpoint
11 Neutral Overcurrent
10 Ground Overcurrent
9 Overcurrent Setpoint
8Aux. Relay Closed
7 New Data in Alarm Log
6Not Used
5Not Used
4Processor Error
3 Energy Value Overflow
2 EEPROM Data Corrupted
1 Function Range Error
0 Calibration Error
Reserved 23
–25 For Future Expansion
1. This register location represents the sequential registers and their numbers within the device itself; as illustrated in Figure 5.1 in Chapter 5, the data
register numbers in the Modbus Master and the DTU3005 unit itself will vary from these register numbers.
Device Command Data Retrieved From PLC (Static Trip III)
First Command Word (Command Word) Second Command Word (Data or Value)
0 = No Command to Perform Unused for Command 0
1 = Reset Kilowatt Demand Unused for Command 1
2 = Reset Kilowatt Hours (Total and Reverse) Unused for Command 2
3 = Close Breaker Unused for Command 3
4 = Open Breaker Unused for Command 4
5 = Clear Targets and Trip Status Unused for Command 5
6 = Close Auxilliary Contact Unused for Command 6
7 = Open Auxilliary Contact Unused for Command 7
Real-Time Device Data Stored in PLC (Static Trip III) (Continued)
Real-Time Data Register Location in
PLC Block
1
Range or Contents