Appendix E: Device Data Format
100 Siemens Energy & Automation, Inc.
General Status Word 3
2
16 Bit Contents
15 AR: Auto-reclose is blocked (Valid)
14 AR: Auto-reclose is blocked (Status)
13 Back-up Overcurrent prot. Is active (Valid)
12 Back-up Overcurrent prot. Is active (Status)
11 Emergency O/C protection is active (Valid)
10 Emergency O/C protection is active (Status)
9 Emergency O/C protection is blocked (Valid)
8 Emergency O/C protection is blocked (Status)
7 Breaker failure protection is active (Valid)
6 Breaker failure protection is active (Status)
5 Earth fault protection is active (Valid)
4 Earth fault protection is active (Status)
3 Earth fault (isol./comp.) reverse dir. (Valid)
2 Earth fault (isol./comp.) reverse dir. (Status)
1 Earth fault (isol./comp.) forward dir. (Valid)
0 Earth fault (isol./comp.) forward dir. (Status)
General Status Word 4
2
17 Bit Contents
15 Dist. teleprotection: Carrier faulty (Valid)
14 Dist. teleprotection: Carrier faulty (Status)
13 Distance Protection is active (Valid)
12 Distance Protection is active (Status)
11 Distance Protection is blocked (Valid)
10 Distance Protection is blocked (Status)
9 Synchro-Check function Faulty (Valid)
8 Synchro-Check function Faulty (Status)
7 Synchro-Check function is blocked (Valid)
6 Synchro-Check function is blocked (Status)
5 AR: Circuit Breaker not Ready (Valid)
4 AR: Circuit Breaker not Ready (Status)
3 AR: Auto-reclose is dynamically blocked (Valid)
2 AR: Auto-reclose is dynamically blocked (Status)
1 AR: Auto-reclose is not ready (Valid)
0 AR: Auto-reclose is not ready (Status)
General Status Word 5
2
18 Bit Contents
12–15 Not Used
11 Overvoltage protection active (Valid)
10 Overvoltage protection active (Status)
9 Switch-onto-fault is active (Valid)
8 Switch-onto-fault is active (Status)
7 Switch-onto-fault is blocked (Valid)
6 Switch-onto-fault is blocked (Status)
5 Weak infeed function is active (Valid)
4 Weak infeed function is active (Status)
3 Weak infeed function is blocked (Valid)
2 Weak infeed function is blocked (Status)
1 Power Swing Detection (Valid)
0 Power Swing Detection (Status)
Number of Last Fault 19 0…32767, 0=no faults
Fault Date/Time (ms) 20 0…59999 (ms )
Fault Date/Time (h/m) 21 High byte: HH (0…23), Low byte: MM (0…59)
Fault Date/Time (m/d) 22 High byte: MM (1…12); Low byte: DD (1…31)
Fault Date/Time (y) 23 Year: YY (00…99)
Interrupted current:
Phase L1 (I/I
n
)
24 ms since fault (-1 = no occurance)
Interrupted current:
Phase L1 (I/I
n
)
25 Low word
Interrupted current:
Phase L1 (I/I
n
)
26 High word
Real-Time Device Data Stored in PLC (7SA513) (Continued)
Function Register Location in
PLC Block
1
Range or Contents