Appendix F: Diagnostic Data Format
134 Siemens Energy & Automation, Inc.
F Diagnostic Data Format
When users select Diagnostic Information to be writ-
ten to the PLC, 6 registers will automatically be
updated in the PLC with the diagnostic information.
The location of this block of 6 consecutive registers in
the PLC is specified by the user.
The format of this register block follows:
Table F.1 Diagnostics Register Block Format
Offset in
Register Block
Register Contents
0 Device communication status for devices 1
–16, 1 bit per device
Bit 0: Set if Device 1 is not communicating
Bit 1: Set if Device 2 is not communicating
...
Bit 14: Set if Device 15 is not communicating
Bit 15: Set if Device 16 is not communicating
1 Device communication status for devices 17
–32, 1 bit per device
Bit 0: Set if Device 17 is not communicating
Bit 1: Set if Device 18 is not communicating
...
Bit 14: Set if Device 31 is not communicating
Bit 15: Set if Device 32 is not communicating
2 Count of “no responses” from ACCESS devices (low order word)
3 Count of “no responses” from ACCESS devices (high order word)
4 Count of responses received from ACCESS devices in which data transmission errors occurred (low order word)
5 Count of responses received from ACCESS devices in which data transmission errors occurred (high order word)