INSTALLATION UM344-2
September 1995
4
-
4
4.3.3.1 Analog Mode
Ÿ The Transmitter outputs a 4-20 mA signal for input to devices such as controllers and recorders.
Ÿ Analog operation employs a Point-To-Point Network comprising a Transmitter, Primary/Secondary
Master, and other non-signaling devices. Transmitter short address is 0 (zero).
Ÿ Use the optional Digital Meter for local indication of transmitter output.
Ÿ The Transmitter is factory configured for analog mode unless otherwise ordered.
Ÿ Use an MXC for configuration, diagnostics, and reporting the current process variable.
4.3.3.2 Digital Mode
Ÿ The number of Allowable Network Elements is:
Primary and Secondary Masters - 1 each
Transmitters - 1 to 15
Ÿ The process variable is transmitted digitally. The analog output of each transmitter is "parked" at 4
mA.
Ÿ The HART communication source can be a Primary or Secondary Master. A Primary Master can be
used for data acquisition, maintenance, or control purposes. A Secondary Master, the MXC for
example, may be used for configuration, diagnostics, and reporting current process variable.
Ÿ Use the optional Digital Meter for local indication of transmitter output.
Ÿ Place the transmitter in the digital mode by assigning it a SHORT ADDRESS from 1 to 15 when
configuring the TRANSMITTER ID BLOCK with the MXC (see Section 5).