8-13
Distributed I/O System DP/ASi Link
EWA 4NEB 710 6055-02b
Station status 3 is reserved for later applications. Its value is always 00
H
.
This byte contains the station number of the DP master which assigned pa-
rameters to the DP slave. Only this DP master has read and write access to
this DP slave.
The default value of the station number during startup is FF
H
. This means
that the DP/ASi link has so far not been assigned parameters by any DP mas-
ter.
The manufacturer ID enables you to precisely identify the DP slave. The
manufacturer ID is specific to a product.
The manufacturer ID for the DP/ASi link has a value of 32795 (801B
H
).
Station status 3
Station number of
DP master
Manufacturer ID