EWA 4NEB 710 6055-02b
The following example shows the structure of the five bytes of data (bytes 15
to 19) for a DP/ASi link having only outputs.
Byte
Value Meaning
15 83
H
Specific identification format:
there follows a length byte for output data
no input data are present
there follow three bytes of manufacturer-specific iden-
tification
16 04
H
Length byte for output data:
dats format: byte
byte consistency
output length: 5 bytes
17 00
H
Manufacturer-specific data
18 3C
H
19 40
H
Example 3
Configuration Message