programmed usage. The label slides behind a clear
protective membrane. One of the LED's assigned to each
switch is a dual color LED used to indicate what type of
signal is active.
Each SCM-8 and each switch is fully programmable and
may be used to control speaker circuits, and awide range
of general system functions such as All Call, All Evac,
Warden's Page, Speaker, etc. Anynumber of circuits may
be grouped and controlled bya single switch. Switch
usages and zone groupings are assigned using the ZEUS
system programmingsoftware.The SCM-8s are mounted
on a hinged panel as a partof the FireFinder XLS Command
Console enclosure.
LCM-8 LED Control Module
The LCM-8 is an FireFinder XLS option module which
provides LED annunciation of system activity. Each LCM-
8 module contains eight groups of 2 LED's, each of which
can be assigned to desired outputs using the ZEUS
programming software. Eight LED's are dual color capable
of being lighted either RED or GREEN flashing or steady.
The remaining LED's are AMBER flashing or steady. A
space is provided for labeling of LED functions. The label
slides behind a clear protective membrane. The LCM-8
dimensions are identical to the SCM-8 and is mounted on
the same hinged panel as a part of the FireFinder XLS
Command Console enclosure.
FCM-6 Fan, Motor, dampers Control Module
The FCM-6 is an FireFinder XLS command console option
module that provides manual control of building HVAC
system fans, motors, and dampers. EachFCM-6 module
provides (6) sets of (3) push button switches for manual
system control. Each switch has3 associated LEDs to
LCM-8
FCM-6
indicate Fan/Damper/Motor status: OFF (Red LED), ON
(Green LED), TROUBLE(Yellow LED).
PSC-12 Power Supply Charger Module
The PSC-12 is a high current power supply that provides
the FireFinder-XLS primary regulated 24VDC power to
operate. It is rated at 12Amps (Alarm)/5Amps (Standby)
and has a built in battery charger capable of charging up to
100AH batteries. The PSC-12 is an addressable intelligent
microprocessor controlled module that communicates it
status to the system operator interface (PMI). The PMI is
able to query the status of the power supply to obtain
information regarding system charging current, terminal
loading information, ground fault conditions and more.
PSC-12 Power Supply Charger Module
PTB Power Termination Board
The PSC-12 comes packaged with a module called the
PTB. The PTB is the Power Termination Board and is
required for operation with the PSC-12. The PTB filters the
power from the incoming AC mains and distributes it to
the PSC-12 power supply and the optional PSX-12 power
supply extender.
The PTB has an optional connector that can be used during
system installation, commissioning & service to provide
the technician with a place to plug in their laptop computer
if required. The AC-ADPT is an optional accessory cable
that allows connection on one side to the PTB via a keyed
connector and on the other end directly into to the laptop's
transformer. Most laptop computer external power trans-
formers have removable AC power cords which can be
replaced by the AC-ADPT to temporarily provide an AC
power source for laptop computer used during system
installation, service and maintenance calls when needed.
PTB Power Termination Board
Commenti su questo manuale