CRC-6 Controllable Relay Card
The Controllable Relay Card (Model CRC-6) is used with
the FireFinder XLS Fire Alarm Control Panel. It is designed
to provide auxiliary control of building functions such as
door holder release, elevator capture, smoke control, lock
release, etc. The CRC-6 plugs into one slot in the CC-5 or
CC-2 Card Cage. It provides six fully programmable relays.
Each relay contains one set of SPDT contacts rated at 4
Amps 30 VDC/120 VAC resistive and 3.5 amps 120 VAC
inductive (0.6 P.F.).
SIM-16 Supervised Input Module
The SIM-16 Supervised input Module is a remotely
located, general-purpose input module. It provides sixteen
input circuits for remote system monitoring. Each input
can be individually programmed as supervised (dry contact
only) or unsupervised (general purpose input.) The SIM-16
has two Form C relays. The relays and inputs are pro-
grammed using the Zeus system programming tool.
rooms. Also, the CDC-4 can be used to upgrade Siemens
conventional fire alarm panels to the FireFinder XLS
system without requiring detector replacement.
CC-5/CC-2 Card Cages
The CC-5/CC-2 card cages provide the physical mounting
location and all wiring connection points for all fire and
voice system options cards for the FireFinder-XLS system.
The CC-5 has 5 slots and the CC-2 has two slots.
All cards plugged into the CC-5/CC-2 card cage communi-
cate with other FireFinder-XLS modules via a common data
bus. Connectors are provided on the left & right side of the
CC-5 to connect a (60) pin cable for communications with
the FireFinder-XLS's operator interface, power supplies and
amplifiers modules.
All field wiring to devices and circuits terminates on the
CC-5/CC-2 card cage. All cards designed for use with the
CC-5/CC-2 route their field wiring terminations to the "top"
of the CC-5/CC-2. These connections are all power limited.
Internal wiring connections distribute 24VDC to cards or
high level audio signals (depending on application used)
connect to the "bottom" of the CC-5/CC-2. These connec-
tions are all non-power limited.
All wiring connections to the CC-5/CC-2 are to removable
terminal blocks. Terminal blocks are rated for use with wire
sized 12AWG to 24AWG. Each connector is numbered to
make wiring terminations to the correct position on the
terminal block simple and reduce the potential for wiring
errors.
CRC-6 Controllable Relay Card
SIM-16 Supervised Input Module
CC-5 Card Cage-5 SlotsCC-2 Card Cage-2 Slots
SCM-8
CDC-4
The Model CDC-4 Conventional Detector Card is used to
monitor Siemens Fire Safety conventional detectors on the
FireFinder XLS system. The CDC-4 can be used in applica-
tions where conventional detectors are more suited than
addressable detectors, like hallways or large meeting
CDC-4
SCM-8 Switch Control Module
The SCM-8 is a FireFinder XLS option module which
provides manual control of the Emergency Voice Evacua-
tion System or manual fire system control. Each SCM-8
module provides eight momentary pushbutton switches
and 16 LED's to indicate their status. Each switch is
assigned two LED's and a label to indicate the switch's
Commenti su questo manuale