Appendix C: Device Data Format
Siemens Energy & Automation, Inc. 73
General Status Word 3
1
16 Bit Contents
6–15 Not used
5 Dist. teleprotection: Carrier faulty (Valid)
4 Dist. teleprotection: Carrier faulty (Status)
3 AR: Auto-reclose is not ready (Valid)
2 AR: Auto-reclose is not ready (Status)
1 Emergency O/C protection is running (Valid)
0 Emergency O/C protection is running (Status)
Number of last fault 17 0…32767, 0 = no faults
Fault Date/Time (ms) 18 0…59999 (ms)
Fault Date/Time (h/m) 19 High byte: HH (0…23), Low byte: MM (0…59)
Fault Date/Time (m/d) 20 High byte: MM (1…12); Low byte: DD (1…31)
Fault Date/Time (y) 21 Year: YY (00…99)
Interrupted current:
Phase L1 (I/I
n
)
22 ms since fault (-1 = no occurrence)
Interrupted current:
Phase L1 (I/I
n
)
23 Low word
Interrupted current:
Phase L1 (I/I
n
)
24 High word
Interrupted current:
Phase L2 (I/I
n
)
25 ms since fault (-1 = no occurrence)
Interrupted current:
Phase L2 (I/I
n
)
26 Low word
Interrupted current:
Phase L2 (I/I
n
)
27 High word
Interrupted current:
Phase L3 (I/I
n
)
28 ms since fault (-1 = no occurrence)
Interrupted current:
Phase L3 (I/I
n
)
29 Low word
Interrupted current:
Phase L3 (I/I
n
)
30 High word
Fault Resistance, Ohm Prim. 31 ms since fault (-1 = no fault)
Fault Resistance, Ohm Prim. 32 Low word
Fault Resistance, Ohm Prim. 33 High word
Fault Reactance, Ohm Prim. 34 ms since fault (-1 = no fault)
Fault Reactance, Ohm Prim. 35 Low word
Fault Reactance, Ohm Prim. 36 High word
Fault Resistance, Ohm Sec. 37 ms since fault (-1 = no fault)
Fault Resistance, Ohm Sec. 38 Low word
Fault Resistance, Ohm Sec. 39 High word
Fault Reactance, Ohm Sec. 40 ms since fault (-1 = no fault)
Fault Reactance, Ohm Sec. 41 Low word
Fault Reactance, Ohm Sec. 42 High word
Distance to fault in km 43 ms since fault (-1 = no fault)
Distance to fault in km 44 Low word
Distance to fault in km 45 High word
Distance to fault in % 46 ms since fault (-1 = no fault)
Distance to fault in % 47 Low word
Distance to fault in % 48 High word
Real-Time Device Data Stored in PLC (7SA511) (Continued)
Function Register Location in
PLC Block
Range or Contents