Siemens DTU3005-B Manuale dell'Operatore Pagina 61

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
Vedere la pagina 60
Appendix C: Device Data Format
Siemens Energy & Automation, Inc. 57
C.2 Device Type: 4300 Power Meter
Real-Time Device Data Stored in PLC (4300 Power Meter)
Real-Time Data Register Location in
PLC Block
Range or Contents
Power Factor 0 0...1000, 0.1 percent
PF Lag/Lead 1 0 = Unity, 1 = Lag, 2 = Lead
Voltage L-N Phase A 2
3 0...999999 V
Voltage L-N Phase B 4
5 0...999999 V
Voltage L-N Phase C 6
7 0...999999 V
Voltage L-L Phase AB 8
9 0...999999 V
Voltage L-L Phase BC 10
11 0...999999 V
Voltage L-L Phase CA 12
13 0...999999 V
Current Phase A 14 0...65000 A
Current Phase B 15 0...65000 A
Current Phase C 16 0...65000 A
Kilowatts 17
18 -999999...999999 kW
Kilowatt Demand 19
20 -999999...999999 kW Max
Maximum Kilowatt Demand 21
22 -999999...999999 kW
Kilowatt Hours (net) 23
24 -999999999...999999999 kWH
Frequency 25 0...32767, 0.1 Hz
Kilovolt-Amperes 26
27 0...999999 kVA
Kilovolt-Amperes Reactive 28
29 0...999999 kVAR
Reserved 30
33 For Future Expansion
Device Command Data Retrieved From PLC (4300 Power Meter)
First Command Word (Command Word) Second Command Word (Data or Value)
0 = No Command to Perform Unused for Command 0
1 = Reset Max Kilowatt Demand Unused for Command 1
2 = Reset Kilowatt Hours Unused for Command 2
Vedere la pagina 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 119 120

Commenti su questo manuale

Nessun commento