Technical specifications (continued)
Input ranges (rated values),
resistance thermometers
• Pt 100 Yes Yes
Thermocouple (TC)
• for thermocouples Type B, J, K, R, S Type B, J, K, R, S
• Temperature compensation
- internal temperature
compensation
Yes; Parameterizable Yes; Parameterizable
- external temperature c
ompensation with Pt100
Yes; Parameterizable Yes; Parameterizable
Resistance thermometer (RTD)
• Characteristic linearization
- for resistance thermometer Pt100 (standard) Pt100 (standard)
Characteristic linearization
• Parameterizable Yes Yes
Cable length
• Cable length, shielded, max. 200 m; 50 m at 80 mV and thermocouples 200 m; 50 m at 80 mV and thermocouples
Analog outputs
Number of analog outputs 16
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current,
max.
25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
• 0 to 10 V Yes
• -10 to +10 V Yes
Output ranges, current
• 0 to 20 mA Yes
• -20 to +20 mA Yes
• 4 to 20 mA Yes
Connection of actuators
• for voltage output
2-conductor connection
Yes
• for current output
2-conductor connection
Yes
Load impedance
(in rated range of output)
• with voltage outputs, min. 1kΩ
• with voltage outputs, capacitive load,
max.
1µF
• with current outputs, max. 500 Ω
• with current outputs, inductive load,
max.
1mH
Cable length
• Cable length, shielded, max. 200 m; 50 m at 80 mV and thermocouples
Analog value creation
Measurement principle integrating integrating
Integrations and conversion time/
resolution per channel
• Resolution with overrange
(bit including sign), max.
14 bit; 12 or 14 bit, parameterizable 14 bit; 12 or 14 bit, parameterizable
• Conversion time (per channel)
16.67 ms; for 12 bit: 16 2/3 ms for 60 Hz, 20 ms for 50 Hz;
for 14 bit: 100 ms for 50 and 60 Hz
16.67 ms; for 12 bit: 16 2/3 ms for 60 Hz, 20 ms for 50 Hz;
for 14 bit: 100 ms for 50 and 60 Hz
Settling time
• for resistive load 0.2 ms 0.1 ms
• for capacitive load
3.3 ms 3.3 ms
• for inductive load
0.5 ms 0.5 ms
6ES7 455-0VS00-0AE0 6ES7 455-1VS00-0AE0
Kap_06_eng.book Seite 87 Donnerstag, 2. Mai 2013 4:16 16