SIMATIC S7-400
Communication
CP 443-1 Advanced
6/117
Siemens ST 70 · 2013
■
Technical specifications (continued)
Amount of data
• as useful data for remote intercon-
nections with input variables in the
case of acyclic transmission with
PROFINET CBA
8 Kibyte
• as useful data for remote intercon-
nections with output variables in the
case of acyclic transmission with
PROFINET CBA
8 Kibyte
Performance data
PROFINET CBA
remote connection
with cyclic transmission
Updating time of the remote intercon-
nections in the case of acyclic trans-
mission with PROFINET CBA
10 ms
Number of remote connections to
input variables with cyclic transmis-
sion with PROFINET CBA maximum
250
Number of remote connections to out-
put variables with cyclic transmission
with PROFINET CBA maximum
250
Amount of data
• as useful data for remote intercon-
nections with input variables in the
case of cyclic transmission with
PROFINET CBA max.
2 000 byte
• as useful data for remote intercon-
nections with output variables in the
case of cyclic transmission with
PROFINET CBA maximum
2 000 byte
Performance data
PROFINET CBA
HMI variables via PROFINET
acyclic
Number of connectable HMI stations
for HMI variables with acyclic trans-
mission with PROFINET CBA
3
Updating time of the HMI variables in
the case of acyclic transmission with
PROFINET CBA
500 ms
Number of HMI variables with acyclic
transmission with PROFINET CBA
maximum
200
Amount of data as useful data for HMI
variables in the case of acyclic trans-
mission with PROFINET CBA maxi-
mum
8 Kibyte
Performance data
PROFINET CBA
device-internal connections
Number of internal connections with
PROFINET CBA maximum
300
Data volume of internal connections
with PROFINET CBA maximum
2 400 byte
Performance data
PROFINET CBA
connections to constants
Number of connections to constants
with PROFINET CBA maximum
500
Amount of data as useful data for inter-
connections with constants in the case
of PROFINET CBA maximum
4 000 byte
Performance data
PROFINET CBA
PROFIBUS proxy functionality
Product function with PROFINET CBA
PROFIBUS proxy functionality
No
Order No. 6GK7 443-1GX30-0XE0
Product-type designation CP 443-1 Advanced
Product functions management,
configuration
Product function MIB support Yes
Protocol is supported
•SNMP v1 Yes
• DCP
Yes
• LLDP
Yes
Configuration software
• required STEP 7 V5.5 SP2 HF1 or higher, or
STEP 7 V11.0 or higher
• for PROFINET CBA required
SIMATIC iMap V3.0 SP1 and higher
Identification & maintenance
• I&M0 - device-specific information -
• I&M1 - plant identification/location
name
-
Product functions Diagnosis
Product function Web-based
diagnostics
Yes
Product functions switch
Product feature switch Yes
Product function
• switch-managed No
• for IRT PROFINET IO switch
Yes
• Configuration with STEP 7
Yes
Product functions Redundancy
Product function
• Ring redundancy Yes
• Redundancy manager
Yes
• MRP redundancy protocol
Yes
Product functions Security
Design of the firewall stateful inspection
Product function with VPN connection
IPSec
Type of encryption algorithms with
VPN connection
AES-256, AES-192, AES-128,
3DES-168, DES-56
Type of authentication procedure with
VPN connection
Preshared key (PSK),
X.509v3 certificates
Type of hashing algorithms with VPN
connection
MD5, SHA-1
Number of possible connections for
VPN connection
32
Product function
• password protection for Web appli-
cations
Yes
• ACL - IP-based
Yes
• ACL - IP-based for PLC/routing
Yes
• switchoff of non-required services
Yes
• blocking of communication via
physical ports
Yes
• log file for unauthorized access
No
Product functions Time
Product function
•SICLOCK support Yes
• pass on time synchronization
Yes
Protocol is supported NTP
Yes
Order No. 6GK7 443-1GX30-0XE0
Product-type designation CP 443-1 Advanced
Kap_06_eng.book Seite 117 Donnerstag, 2. Mai 2013 4:16 16
© Siemens AG 2013
Commenti su questo manuale