Specifications
Power Supply Rated Inputs Meter
Maximum Steady State
Dielectric
Withstand
VA W VA W
Standard AC / DC
Power Supply
AC: 100 – 240 VAC, 50 – 60 Hz
DC: 110 – 300 VDC
Installation category II (Local).
Pollution degree 2.
Integrated 13 8 8 5
2000 VAC RMS,
60 Hz for 1 minute
TRAN / RMD13895
TRAN 5353
Low Voltage DC
Power Supply
20 – 60 VDC
Integrated 6 4
TRAN / RMD 7 5
TRAN 3 3
480V Power Supply
480 VAC, 60 Hz
Installation category III
(Distribution). Pollution degree 2.
Integrated 15 12 12 10
3250 VAC RMS,
60 Hz for 1 minute
TRAN / RMD 15121310
TRAN 11 9 11 9