Metasys Integrator—Metasys Integrator Siemens Application 11
Metasys Integrator Unit Setup
To set up the Metasys Integrator unit, you use a portable PC connected to
Metasys Integrator Terminal Port. Metasys Integrator unit setup involves:
• downloading the correct vendor communication table (.VCT file)
• setting up the ports
• assigning network addresses to the controllers
The following table provides setup information specific to Siemens
applications. For detailed procedures, see the Metasys Integrator unit
technical bulletins.
Table 3: Metasys Integrator Unit Setup for Siemens SEAbus
Applications
Vendor Communication Table (.VCT File)
Model 4300 Power Meter
SI_4300.VCT
Model 4700 Power Meter
SI_4700.VCT
Trip III/CPNX
SI_CPX.VCT
SAMMS Protective Relay
SI_SAMMS.VCT
Access I/O Addressable Relay
SI_ACCIO.VCT
Port Setup
Baud Rate
9600
Word Length
8
Stop Bit
1
Parity
None
Interface
RS-485
Network Setup
Vendor Address
0-254
Timeout Value
1000 ms
Poll Delay
Model 4300 Power Meter
Model 4700 Power Meter
Static Trip III/CPNX
SAMMS
Access I/O Addressable Relay
110 ms
110 ms
110 ms
110 ms
110 ms
Performance Guide
Approximate Scan Time for a Single
N2 Address
Model 4300 Power Meter
Model 4700 Power Meter
Static Trip III/CPNX
SAMMS
Access I/O Addressable Relay
1 second
2 seconds
2 seconds
1 second
1 second