Distributed Use of SIMATIC FS600 Laser
Scanner in Category 3 / SIL 2
Entry ID: 21330889
A&D Safety Integrated Page 11/51 AS-FE-I-010-V20-EN
Copyright © Siemens AG 2007 All rights reserved
21330889_as_fe_i_010_v20_en_lscanner.doc
Flowchart
The flowchart illustrates the function process of the safety functional
example.
NOTICE
In order to meet the requirements of category 3 / SIL 2, it is
obligatory for certain actuators (e.g. contactor) to read back the
process signal to the actuator.
Read-back is not implemented in this safety functional example. The
actuator is an indicator light simulating a machine. When using
different actuators, the feedback circuits have to be integrated and
evaluated by the user. Safety functional example 7 provides a
detailed description of “Read back”.