7ML19981FC01 HydroRanger 200 – INSTRUCTION MANUAL Page 177
mmmmm
Parameters
P708 Volume Rate Display
The rate of change of volume in percent of maximum volume per minute.
This value is used internally to calculate inflow in pumped volume applications (P622=3).
Press READING to toggle between percent and volume.
Measurement Verification (P710 to P713)
P710 Fuzz Filter
Use this to stabilize the reported level, due to level fluctuations (such as a rippling or
splashing liquid surface) within the Echo Lock Window (P713).
This value (in % of Span, P007) is automatically altered when Maximum Process Speed
(P003) is altered. The higher the value entered, the greater the fluctuation stabilized.
P711 Echo Lock
Use this feature to select the measurement verification process.
Primary Index Global
Values Range: -999 to 9999 (view only)
Related P622 Inflow / Discharge Adjust
Primary Index Global
Values Range: 0 to 100 (0 = off)
Altered by P003 Maximum Process Speed
Related P007 Span P713 Echo Lock Window
Primary Index Global
Values
0Off
1 Maximum verification
2 * Material agitator
3Total lock
Related
P700 Max Fill Rate
P701 Max Empty Rate
P712 Echo Lock Sampling
P713 Echo Lock Window
P820 Algorithm
Vedere la pagina 190
1 2 ... 186 187 188 189 190 191 192 193 194 195 196 ... 255 256

Commenti su questo manuale

Nessun commento

Online-power Proveedores De Energía manuales de usuario

Empezando en T

Haga clic en el alfabeto a continuación para desplazarse a la lista completa de modelos que comienzan con esa letra

Modelos Tipo de documento
Telecommunication
Manual de usuario   OnLine Power Telecommunication User Manual, 57 paginas