Siemens S7-400PLC Specifiche Pagina 114

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 486
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 113
Digital modules
4.8 Digital input module SM 421; DI 16 x DC 24 V (6ES7421-7BH01-0AB0)
S7-400 Automation System Module Data
114 Reference Manual, Edition 09/2009, A5E00850736-06
Time, Frequency
Internal preparation time
1
for
Status identifier only
Input delay of the channel group 0.05 ms/0.05 ms
Input delay of the channel group 0.05 ms/0.1 ms
or 0.1 ms/0.1 ms
Input delay of the channel group ≥ 0.5 ms
Maximum 50 µs
maximum 70 µs
maximum 180 µs
Status identifier and hardware interrupt enable
Input delay of the channel group 0.05 ms/0.05 ms 2)
Input delay of the channel group 0.05 ms/0.1 ms
or 0.1 ms/0.1 ms
Input delay of the channel group ≥ 0.5 ms
Maximum 60 µs
maximum 80 µs
maximum 190 µs
Internal preparation time for diagnostics/diagnostic
interrupt
Max. 5 ms
Input delay
Programmable
Yes
Nominal value
0.05 / 0.1 /0.5 / 3 ms
Input frequency
(with a time delay of 0.1 ms)
< 2 kHz
Values go into cycle and response times.
Sensor Circuit
Resistance circuit of the sensor for wire break
monitoring
10 kΩ to 18 kΩ
1
The filter times are added to the overall runtime of the selected input delay.
2
Substitute functionality; diagnostics and diagnostic interrupt are not to be selected.
Vedere la pagina 113
1 2 ... 109 110 111 112 113 114 115 116 117 118 119 ... 485 486

Commenti su questo manuale