The control program for each TC Compact
is
customized to exactly match the application. Proven
Powers Process Control Language (PPCL), a text-
based programming structure like BASIC, provides
direct digital control and energy management
sequences to precisely control equipment and
optimize energy usage.
Global Information Access
The HMI port supports operator devices, such as a
local user interface or simple CRT terminal, and a
phone modem for dial-in service capability. Devices
connected to the operator terminal port gain global
information access.
Multiple Operator Access
Multiple operators can access the network
simultaneously. Multiple operator access ensures that
alarms are reported to an alarm printer while an
operator accesses information from a local terminal.
When using the BACnet/IP ALN option, multiple
operators may also access the controller through
concurrent Telnet sessions and/or local operator
terminal ports, plus optional Web interface using the
Web or Web Services option.
Menu Prompted, English
Language Operator Interface
The TC Compact includes a simple, yet powerful,
menu-driven English Language Operator Interface
that provides, among other things:
Point monitoring and display
Point commanding
Historical trend collection and display for multiple
points
Event scheduling
Program editing and modification via Powers
Process Control Language (PPCL)
Alarm reporting and acknowledgment
Continual display of dynamic information
Built-in Direct Digital Control
Routines
The TC Compact provides stand-alone Direct Digital
Control (DDC) to deliver precise HVAC control and
comprehensive information about system operation. It
receives information from sensors in the building,
processes the information, and directly controls the
equipment. The following functions are available in
the TC Compact:
Closed Loop Proportional, Integral and Derivative
(PID) control.
Logical sequencing.
Alarm detection and reporting.
Reset schedules.
Built-in Energy Management
Applications
The following applications are programmed in the TC
Compact Series and require simple parameter input
for implementation:
Automatic Daylight Saving Time switchover
Duty cycling
Economizer control
Event scheduling
Holiday scheduling
Night setback control
Peak Demand Limiting (PDL)
Temperature-compensated duty cycling
Temporary schedule override