Siemens Protection Devices Limited 13
Ordering Information
Product description Variants Order No.
Nondirectional O/C Relay 7
S
R
1
1
0
2
-
1 □
A
1 2 - □
A
A
0
▲ ▲
▲
▲ ▲▲
▲
▲▲
Overcurrent – Non Directional 1 | | | | | | | |
| | | | | | | |
Case I/O and Fascia | | | | | | | |
E4 case, 4 CT, 3 Binary Inputs / 5 Binary Outputs, 10 LEDs 2 | | | | | | |
| | | | | | |
Measuring Input | | | | | | |
1/5 A, 50/60Hz
1)
1 | | | | | |
| | | | | |
Auxiliary voltage | | | | | |
80 to 250V DC, binary input threshold 19V DC G | | | | |
80 to 250V DC, binary input threshold 88V DC H | | | | |
24 to 60V DC, binary input threshold 19V DC J | | | | |
| | | | |
Communication Interface | | | | |
Standard version – included in all models, USB front port RS485 rear port 1 | | | |
| | | |
Protocol | | | |
IEC 60870-5-103 and Modbus RTU and DNP3 (user selectable setting) 2 | | |
| | |
Relay Cover | | |
Standard Version – No Push Buttons 1 ||
Push Buttons – Down and Right Arrows 2 ||
||
Protection Function Packages ||
Basic version
46BC Broken conductor/load unbalance
50 Instantaneous phase fault overcurrent
50BF Circuit breaker fail
50G/50N Instantaneous earth fault
51 Time delayed phase fault overcurrent
51G/51N Time delayed earth fault
60CTS
CT Supervision
64H High Impedance REF
74T/CC Trip & Close circuit supervision
86 Lockout
Programmable logic
A |
|
|
|
|
|
|
|
|
|
|
|
|
|
Additional Functionality |
No Additional Functionality A
1)
4CT is configured as 3PF + EF