Siemens Advance Network Gateway Manuale Utente Pagina 30

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 88
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 29
CE Installations, Continued
3. A split ferrite must be clamped to Data Hiway cables and fixed
immediately to the outside of the ANG_EN; use part number
1173000-013 ferrite contained in CE Installation Kit. This is required
to meet the Conducted Immunity requirement for CE/EMC Heavy
Industrial. All other CE/EMC Heavy Industrial requirements are met
without the use of a ferrite clamp.
4. Shielded Ethernet cable must be used for all Ethernet connections,
in and outside the GC, and coupled through the enclosure using a
shielded RJ-45 coupler; use part number 1183200-003 contained in
CE Installation Kit. A mounting plate (part number 2020261-001) is
also available to accomplish this. If needed for Zone 1 installation
part numbers 2017984-001 and 2017985-001 is available to maintain
purge. If a PG gland is used to make the 360-degree termination of
the Ethernet shield at the enclosure, the Installation Kit and other
parts are not required.
16 Installation 2000590-001
Vedere la pagina 29
1 2 ... 25 26 27 28 29 30 31 32 33 34 35 ... 87 88

Commenti su questo manuale

Nessun commento