Siemens Advance Network Gateway Manuale Utente Pagina 63

  • Scaricare
  • Aggiungi ai miei manuali
  • Stampa
  • Pagina
    / 72
  • Indice
  • SEGNALIBRI
  • Valutato. / 5. Basato su recensioni clienti
Vedere la pagina 62
DataNET Troubleshooting Guide, Continued
Configuration
Parameter Errors
The device may have an invalid or duplicate IP address, Subnet mask or
iproute. Each ANCB must have a
unique IP address. Verify the
configuration parameters by connecting a PC serial port to the
Configuration Port, Logging in and typing config display.
local> config display
Config:
Device ANCB_DN
address ip 172.16.9.239
netmask 255.255.0.0
address ethernet 00.c0.c9.00.d2.3b
iproute 0.0.0.0
time server ip 0.0.0.0
port1 DataNET Copper
port2 DataNET Copper
Device ID
The ANCB/DN device id is automatically assigned and is not user
configurable as it is on the DataNET Hub. Th ANCB/DN device ID is
automatically set to the board IP address at power up or reset. :
Broadcast Status
Information
The Advance Network device periodically broadcast their status for
diagnostic and network routing purposes.
2000592-001 Troubleshooting 53
Vedere la pagina 62
1 2 ... 58 59 60 61 62 63 64 65 66 67 68 ... 71 72

Commenti su questo manuale

Nessun commento